COMMANDS AND FUNCTIONS:

Genset status: OFF, MAN, AUTO, TEST;

Fuel refilling pump status: OFF, MAN, AUTO;

Manual or Programmable Start/Stop;

Remote Start/Stop;

Manual command opening / closing GCB and MCB;

Manual command START ON/STOP ON;

16 programmable time-out (or countdown) for maintenance (per hour and months);

Monitoring output of coil relay continuity outputs;

GCB and MCB feedback monitoring;

CANbus SAE J1939 communication monitoring

BLACK BOX: 2500 events;

4 graphic TREND (choose among 40 measurements);

HELP with descriptions and solutions for recorded problems;

Acoustic alarm;

Date and clock with battery.

 

APPLICATIONS:

SPM: single prime mover;

SSB: single stand-by.

 

COMMUNICATION with external hardware:

1 CANbus for SAE J1939 opto-isolated for engine communication;

1 proprietary CANbus opto-isolated for Guard Touch communications;

1 RS485 for GSM communications, PC monitoring, MODbus, Ethernet connection;

1 RS485 for external connection, battery charger, remote alarm card, expansion board I/O.

COMANDI E FUNZIONI

Stati gruppo: OFF, MAN, AUTO, TEST;

Stati pompa caricamento carburante: OFF, MAN, AUTO;

Start/Stop manuale o Programmabile;

Start/Stop da remoto

Comando manuale apertura / chiusura GCB e MCB

Comando manuale START/STOP;

16 time-out programmabili di manutenzione in ore e mesi;

Monitoraggio continuità bobina relè uscite;

Monitoraggio feedback GCB e MCB;

Monitoraggio comunicazione CANbus SAE J1939 BLACK BOX: 2500 eventi;

4 TREND grafici selezionabile tra 40 misure;

HELP in linea di descrizione e causa e soluzione dei problemi registrati;

Allarme sonoro;

Datario con batteria tampone.

 

TIPI DI IMPIANTI GESTITI:

SPM: single prime mover;

SSB: single stand-by.

 

COMUNICAZIONI CON PERIFERICHE:

1 CANbus per SAE J1939 optoisolato;

1 CANbus proprietario per comunicazioni Guard Touch optoisolato;

1 RS485 per collegamento GSM, monitoraggio PC, MODbus, connessione Ethernet;

1 RS485 per collegamento periferiche, carica batterie, scheda remota allarmi, schede espansioni I/O.

Functions

DISPLAY TOUCH SCREEN FEATURES:

Display black and white with 16 grey tones

Touch screen Tecnology

Dimension: 320 (W) x 240 (H) pixels - 6 inch diagonal

Range of operation -20°C +70°C

 

DISPLAY TOUCH CARATTERISTICHE TECNICHE

Display Bianco e nero con 16 livelli di grigio

Tecnologia Touch screen

Dimensioni: 320 (L) x 240 (H) pixels - 6 pollici

Range operativo -20°C +70°C

Display

Measurements and protection

MAINS measurements:

Voltage VAC mains: L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N; Lx-N  <= 300V (RMS); Lx-N;= 300V (RMS).

 

GENSET measurements:

Voltage VAC genset: L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N; Lx-N  <= 300V (RMS); Lx-N;= 300V (RMS);

Currents: L1, L2, L3, - L4 (RMS);

Active power: sum and per each phase;

Apparent power: sum and per each phase;

Reactive power: sum and per each phase;

Power factor: average and per each phase;

Active energy produced: sum and per each phase;

Battery voltage VDC;

Battery charger current (up to max 2 bc);

Speed;

Working hours;

Rental hours (for rent applications);

Starting attempts counter;

Successful starts in %;

ACB MCB manoeuvres counter;

Coolant liquid temperature ;

Oil pressure/Oil temperature;

Engine exhaust temperature main bearings 1/2

Fuel level in % ;

Engine power used in %;

Air turbo pressure, Air turbo temperature

Immediate fuel consumption; Fuel consumption from the last start up; Total fuel consumption (calculated on engine lifespan);

Alternator windings temperature.

 

ALTERNATOR measurements:

Max voltage (59); Min voltage (27);

Max frequency (81U); Min frequency (81O);

Phase sequence error;

Voltage asymmetry; Currents asymmetry;

Energy reversal (32);

Short circuit (50);

Max temperature alternator windings;

Alternator capability: Max kW (51),

Max kVAr inductive and capacitive.

 

MAINS protection:

Max voltage (59); Min voltage (27);

Max frequency (81U); Min frequency (81O);

Phase sequence error;

Voltage asymmetry.

 

ENGINE protections:

Coolant liquid temperature;

Oil pressure; Oil temperature; Oil level;

Low fuel level; Max power;

Over-speed (12);

Broken belt;

Missed start/stop;

Min coolant level;

Visualisation of engine error codes via CANbus SAE J1939.

 

 

MISURE RETE:

Tensione VAC rete: L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N; Lx-N  <= 300V (RMS); Lx-N;= 300V (RMS).

 

MISURE GENERATORE ELETTRICO

Tensione VAC gruppo: L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N; Lx-N  <= 300V (RMS); Lx-N;= 300V (RMS);

Correnti: L1, L2, L3, - L4 (RMS);

Potenza attiva: sommatoria/singola fase

Potenza : sommatoria/apparente/per singola fase;

Potenza reattiva: sommatoria/singola fase;

Fattore di potenza: valore medio/singola fase;

Energia attiva prodotta sommatoria/singola fase;

Tensione VDC batteria;

Correnti carica batterie;

Velocità di rotazione;

Ore lavorate;

Ore noleggio;

Conta avviamenti; %buon fine tentativi di avviamento;

Conta manovre ACB MCB;

Temperatura liquido refrigerante;

Pressione/Temperatura olio;

Temperatura fumi bancata 1/2;

% Livello carburante;

% di potenza in uso del diesel;

Pressione/Temperatura aria turbo;

Consumo carburante istantaneo/da ultimo avviamento/carburante vita motore;

Temperature avvolgimenti alternatore.

 

PROTEZIONI ALTERNATORE:

Massima tensione (59);

Minima tensione (27);

Massima frequenza (81U);

Minima frequenza (81O);

Sequenza fase;

Asimmetria tensione/correnti;

Inversione di energia (32);

Corto circuito (50);

Massima temperatura avvolgimenti alternatore;

Capability alternatore: Max kW (51) - Max kVAr induttivi e capacitivi.

 

PROTEZIONI RETE:

Massima tensione (59);

Minima tensione (27);

Massima frequenza (81U);

Minima frequenza (81O);

Sequenza fase;

Assimetria tensione.

 

PROTEZIONI MOTORE:

Temperatura liquido refrigerante;

Temperatura olio;

Pressione olio; Basso-Alto livello carburante;

Massima potenza; Sovravelocità (12);

Rottura cinghia; Mancato avviamento;

Copyright Visa SpA 2014. All Rights Reserved.